Install Leadbacked Drywall

Lead-lined drywall is installed in areas that require radiation shielding, such as the walls of a PET/CT imaging room. During manufacture, lead sheeting is pressure-laminated to sheetrock gypsum panels. When installed with the specified lead overlapping joints, and with all attaching screws covered with lead discs, the continuous layer of lead behind the drywall provides effective radiation shielding. Because of its weight, and to prevent panels from sagging and cracking, the transportation, storage and handling of lead-lined drywall requires special care.


Instructions


1. Bend a 3-inch-wide lead batten strip 90 degrees lengthwise down the middle. Attach a batten strip vertically into all corners against the studs with the adhesive provided. This will overlap both inside faces of the corner, thus preventing radiation leakage through penetrating corner joints.


2. Attach 2-inch-wide lead batten strips to the surface of all studs, backing vertical and horizontal drywall joints with adhesive. Make sure that the batten strips are positioned to provide a 1-inch overlap on either side of the joint.


3. Prevent drywall cracks by supporting both sides and the middle of the lead-lined drywall while lifting it in place. Place the leaded side of the drywall against the studs.


4. Avoid deforming the lead backing by drilling pilot holes through the sheeting and into the stud with a suitable-size drill bit and cordless drill/driver before inserting the drywall screws. Attach the necessary lead battens to extend edge overlaps at least 1 inch into all frames and openings.


5. Attach lead-shielded drywall to the edge supporting studs with drywall screws inserted equally spaced on 8-inch centers. Screw the drywall to intermediate studs with equally spaced drywall screws on 12-inch centers. Sink in the screw heads sufficiently to dimple the drywall surface.


6. Glue 3/8-inch-diameter lead discs to the heads of all attaching screws with the adhesive provided. All lead discs and batten strips must be of equal thickness to the lead drywall backing.


7. Attach shielding to all receptacle switches, fastener penetrations and penetrating seams as laid down in the building code regulations. Extend shielding battens 1 inch into all door and window openings.


8. Tape, float and finish the walls as required for unshielded drywall.



Related posts



    Lead-lined drywall has a sheet of lead built into it that blocks out radiation. It is commonly used in hospitals and clinical settings that use equipment that produces radiation. You can also use...
    Set screws no more than 1/8 inch below the surface of drywall.Drywall provides an excellent wall surface with its smooth, flat exterior and its pressed gypsum core that increases a room's insulati...
    Warm up your walls with custom installed drywall you hang yourself.There are few wall surfaces that won't look better with the addition of drywall. Sometimes called sheetrock or even gypsum board,...
    Nails won't hold drywall to steel studs.Builders frequently frame new walls in commercial buildings and apartments with steel studs. These studs are lighter than wooden studs, which is important i...
    Curved walls can provide a decorative element to your home.Drywall is a building material made of gypsum board pressed between sheets of paper that is installed over wall studs to finish walls in...